A panel shop drills a 20.0 mm hole for an M20 gland. The gland threads in, but it will not seat flat — the powder coat is 80 microns thick and there is a burr on the back face that nobody removed. The next batch gets drilled at 21 mm instead, and now the O-ring has a 1 mm gap to bridge on one side. Neither panel leaks on the bench. Both leak on site.

Choosing a gland and cutting the hole are two different jobs with two different sets of numbers. This page covers the second one. For which gland matches which cable, the cable gland size chart handles that side.

The Clearance Rule for Cable Gland Drill Size

A cable gland hole is a clearance fit. The thread has to pass through the panel without interference, so the hole is always larger than the thread’s major diameter — typically by 0.2 to 0.5 mm for metric, PG and G threads.

That figure is not arbitrary. The lower limit comes from the thread’s own tolerance: a 6g external thread on a nominal 20 mm diameter has a fundamental deviation of −38 µm, so it can measure 19.96 mm across the flanks. Any hole smaller than the major diameter will bind before the gland seats. The upper limit comes from the seal, not the thread.

For metric, PG and G cable glands the drill or knockout size is the thread’s major diameter plus 0.2 to 0.5 mm of clearance. The lower limit is set by the thread tolerance; the upper limit is set by how much gap the O-ring or sealing washer can still bridge. NPT is the exception — it is a tapped, tapered thread, and its hole is considerably smaller than the thread O.D.

Why the O-ring sets the upper limit

The gland seals against the panel face, not against the hole wall. An O-ring or sealing washer sits on the body flange, compresses against the panel, and has to cover the annular gap between the thread and the hole edge.

An M20 gland typically carries an O-ring with a 20 mm inside diameter and a 2 mm cross-section, giving roughly 24 mm of outside diameter. A 20.5 mm hole leaves 1.75 mm of O-ring covering the gap on each side — comfortable. A 22 mm hole leaves 1.0 mm, and the compression is uneven around the circumference, which is where a slow weep starts.

So the hole cannot be enlarged indefinitely to “make it fit”. Past about 0.5 mm of clearance you are trading thread fit for seal margin.

Why the thread tolerance sets the lower limit

Cut the hole at exactly the nominal diameter and you are relying on the thread being at its low limit. In practice, plating, paint, and the slight ovality that comes from a worn punch all push the effective hole smaller.

A 20.0 mm hole for an M20 gland is a line-to-line fit. It will work on a clean, unpainted, freshly punched panel. Add 80 microns of powder coat inside the hole and it will not.

Cable Gland Drill Size Chart: Metric (M) Thread

Thread outside diameters below are the actual figures for the XingWei brass series. The clearance column is the major diameter plus 0.2–0.5 mm.

ThreadThread O.D. (mm)Clearance hole (mm)
M8 × 1.258.08.2–8.5
M10 × 1.510.010.2–10.5
M12 × 1.512.012.2–12.5
M14 × 1.514.014.2–14.5
M16 × 1.516.016.2–16.5
M18 × 1.518.018.2–18.5
M20 × 1.520.020.2–20.5
M22 × 1.522.022.2–22.5
M24 × 1.524.024.2–24.5
M25 × 1.525.025.2–25.5
M27 × 1.527.027.2–27.5
M28 × 1.528.028.2–28.5
M30 × 1.530.030.2–30.5
M32 × 1.532.032.2–32.5
M36 × 1.536.036.2–36.5
M40 × 1.540.040.2–40.5
M42 × 1.542.042.2–42.5
M47 × 1.547.047.2–47.5
M48 × 1.548.048.2–48.5
M50 × 1.550.050.2–50.5
M54 × 1.554.054.2–54.5
M56 × 1.556.056.2–56.5
M60 × 1.560.060.2–60.5
M63 × 1.563.063.2–63.5
M64 × 264.064.2–64.5
M72 × 272.072.2–72.5
M75 × 275.075.2–75.5
M80 × 280.080.2–80.5
M88 × 288.088.2–88.5
M100 × 2100.0100.2–100.5

The M20 case, which causes the most argument

M20 is the single most common entry size, and 20.5 mm is the number to standardise on. It clears an unpainted panel, it clears a painted panel, and it leaves the O-ring 1.75 mm of coverage on each side.

A 20.0 mm hole works only on bare metal. A 21 mm hole works but eats seal margin. If a shop is already tooled for 20.3 mm punches — a common size — that is fine too, and better than 20.0.

Cable Gland Drill Size Chart: PG Thread

PG thread outside diameters are not round numbers, which is why a PG hole chart never matches a metric punch set.

ThreadThread O.D. (mm)Clearance hole (mm)
PG712.512.7–13.0
PG915.215.4–15.7
PG1118.618.8–19.1
PG13.520.420.6–20.9
PG1622.522.7–23.0
PG1925.025.2–25.5
PG2128.328.5–28.8
PG2532.032.2–32.5
PG2937.037.2–37.5
PG3647.047.2–47.5
PG4254.054.2–54.5
PG4859.359.5–59.8
PG6372.072.2–72.5

PG13.5 and the 20 mm trap

PG13.5 needs a 20.4 mm thread hole, and its clearance range runs 20.6–20.9 mm. An M20 needs 20.2–20.5. The two overlap at the edges but neither will accept the other’s gland, and a shop that standardises on a 20.5 mm punch will find PG13.5 glands bind.

Where a panel carries a mix of metric and PG entries, keep two punch sizes on the bench and label the drawings with the thread standard, not just the number. The guide to metric, PG and NPT thread standards explains why the diameters diverge.

Cable Gland Drill Size Chart: G (PF / BSPP) Thread

G threads are parallel to ISO 228, so the same clearance rule applies. The outside diameters sit noticeably above the nominal fraction — G1/2 is 20.9 mm, not 12.7 mm as the “half inch” label suggests.

ThreadThread O.D. (mm)Clearance hole (mm)
G1/413.113.3–13.6
G3/816.616.8–17.1
G1/220.921.1–21.4
G3/426.426.6–26.9
G133.233.4–33.7
G1¼41.942.1–42.4
G1½47.848.0–48.3
G259.659.8–60.1
G2½75.175.3–75.6
G387.888.0–88.3

NPT Is Not a Clearance Hole

NPT glands are not dropped through a drilled hole. The enclosure entry is tapped with an NPT tap, and the tapered thread seals by wedging into it. The hole is therefore a tap drill size, and it is substantially smaller than the thread outside diameter.

For 1/2″ NPT, the thread outside diameter at the gauge plane is 21.2 mm. The tap drill is 23/32 inch, or 18.3 mm — a difference of nearly 3 mm. For 1-1/2″ NPT the thread measures 48 mm and the tap drill is 1-47/64 inch, or 44.0 mm.

That gap is what the tap cuts away. It also explains why an NPT entry cannot be improvised from a metric hole.

Why re-tapping a metric hole to NPT fails

An M20 hole at 20.5 mm is already larger than the 1/2″ NPT tap drill of 18.3 mm. Running an NPT tap into it produces a thread with almost no material at the crest, which will strip under the torque needed to seat the gland.

Going the other way is no better: an 18.3 mm hole tapped for NPT will not accept an M20 gland at all, because the major diameter is 2 mm undersized.

Where an enclosure already has the wrong thread, use an adaptor rather than re-cutting. It preserves the original thread and adds a known, tested joint.

Knockout, Punch, Hole Saw or Drill: Which to Use

The hole dimension is only half the job. Roundness and burr matter just as much, because the O-ring seals against the panel face around the hole, and an out-of-round hole gives uneven compression.

MethodBest forRoundnessBurrNotes
Hydraulic knockout punchProduction panels, 16–100 mmExcellentMinimalNeeds access to both faces; leaves a clean, slightly rounded edge
Chassis punch (manual)Small runs, thin sheetGoodMinimalSlow above 32 mm
Hole sawSite work, thick enclosuresFairHeavyNeeds deburring on both faces; wanders on thin sheet
Step drillThin sheet, small sizesGoodLightPractical up to about 30 mm
Drilled and tappedNPT entriesGoodLightRequires the correct NPT tap and a gauge check

Punch and knockout sizes

Standard knockout punch sets are sized in the same range as the clearance figures above, and most suppliers offer 20.5, 22.5, 25.5, 32.5 and similar. Where a punch sits at the low end of the clearance range, it is still usable — the constraint is only that the thread must pass and the O-ring must cover.

What a punch set will not do is produce a PG13.5 entry from a metric punch. The 0.4 mm difference between the M20 and PG13.5 thread diameters is enough to bind.

Where a hole saw costs you

A hole saw is the fastest way to open an entry on an installed enclosure, and it is also the most likely to leave a burr on the inside face that nobody can reach afterwards. That burr holds the gland off the panel by a fraction of a millimetre, and the O-ring never compresses evenly.

If a hole saw is the only option, deburr from both sides with a hand tool before fitting, and check the flange sits flat with a straight edge.

Tolerance, Burr and Paint

Three things decide whether a correctly sized hole actually seals.

Burr. Any raised material on the panel face holds the gland flange away from the surface. Deburr both faces, not just the accessible one.

Paint. Powder coat inside the hole reduces the effective diameter and can stop the thread engaging. Powder coat on the face around the hole is worse — it is compressible, uneven, and sits exactly where the O-ring needs a flat land. Either mask the entry before coating or fit a sealing washer designed to bridge it.

Flatness. Cast enclosures often have a draft angle or a raised boss around the entry. An O-ring needs a flat annulus of at least the O-ring’s outside diameter. Where the face is not flat, a flat sealing washer performs better than an O-ring.

Any of these three will produce a gland that weeps with a perfectly correct hole dimension. The common causes of a leaking cable gland covers how to tell them apart once water is already inside.

The O-ring and sealing washer ranges cover both cases, and fitting the wrong one is a common cause of a gland that weeps despite a correct hole.

Wall Thickness and Thread Engagement

The hole size is right and the gland still will not sit down, because the thread is shorter than the wall is thick.

Thread length has to cover the panel wall plus the locknut plus any washer. On a 3 mm sheet panel a standard 8 mm thread is generous; on a 6 mm cast wall the same gland leaves nothing for the locknut.

The practical minimum is two full thread turns of engagement beyond the panel, with the locknut fully seated. Below that the gland can be pulled out under cable load, and the IP rating is meaningless regardless of what the O-ring does.

Where the wall is too thick, the options are a long-thread gland, an internal-thread entry, or a different entry point. All three are cheaper than discovering it after the panel is painted.

Frequently Asked Questions

What size hole do I drill for an M20 cable gland?

20.2 to 20.5 mm. The M20 thread measures 20.0 mm across its major diameter, so the hole needs 0.2–0.5 mm of clearance. 20.5 mm is the safe default for a painted panel; 20.0 mm will bind once powder coat is inside the hole.

Is the cable gland drill size the same as the thread size?

No. The thread size is the nominal diameter of the thread; the drill size is that diameter plus clearance. For parallel threads the difference is small — a few tenths of a millimetre. For NPT the difference is large and in the opposite direction, because the entry is tapped rather than drilled.

What size hole does a PG13.5 cable gland need?

20.6 to 20.9 mm. The PG13.5 thread measures 20.4 mm, which is close enough to M20 that the two are often confused. A 20.5 mm punch that works for M20 will bind on a PG13.5 gland.

Can I drill the hole larger if the gland will not fit?

Only within the clearance range. Enlarging past thread diameter plus about 0.5 mm reduces the width of panel the O-ring or sealing washer has to cover, and an uneven seal is worse than a tight fit. If the gland will not enter, check for burr, paint and thread damage before reaching for a bigger bit.

Does the hole size change for nylon or stainless glands?

The thread is the same, so the clearance hole is the same. What changes is the body geometry — nylon glands often have a wider flange and a larger O-ring, which gives more seal margin around the hole, while stainless bodies are usually slimmer. Check the flange diameter on the datasheet if the entry is close to an edge.

A cable gland drill size is one number derived from another: thread major diameter plus clearance. Once that is understood, the four thread standards stop being a source of confusion and become a lookup — M20 wants 20.2–20.5, PG13.5 wants 20.6–20.9, G1/2 wants 21.1–21.4, and NPT1/2 wants an 18.3 mm tap drill rather than a clearance hole at all.

The remaining variables are the ones a chart cannot fix: deburr both faces, keep paint off the O-ring land, and check that the thread is long enough for the wall. Those three account for most of the entries that leak with a perfectly correct hole dimension.

The cable gland category lists the full range with thread lengths and flange dimensions for each size, and the nickel-plated brass waterproof series covers the metric and PG sizes most panels use. For installation variables that void the seal after the hole is correct, the common causes of IP68 water ingress covers the field cases.