A multi-hole cable gland (also called a multi-cable or multi-entry gland) seals several cables through a single enclosure entry. One body and locknut replace a row of single glands when space on the panel is limited or when a group of small cables shares the same route into the box.

Used correctly, a multi-hole gland saves cut-outs and keeps a clean IP seal. Used incorrectly—wrong hole count, cables outside the seal range, or mixed diameters that never compress evenly—it becomes a leak path. This guide explains when multi-hole glands make sense, how to size them, and what to avoid.

For single-cable selection basics, see What Is a Cable Gland? and the Cable Gland Sizing Guide.

What Is a Multi-Hole Cable Gland?

A multi-hole gland has one threaded body that mounts in a single panel hole, and a sealing insert with two or more openings. Each opening is sized for a defined cable outer-diameter (OD) range. When the compression nut is tightened, the elastomer closes around every cable in its hole at the same time.

Typical configurations include 2, 3, 4, or more holes in one insert. Some designs use split or modular inserts so cables can be fitted without full threading from the free end. Materials are usually nickel-plated brass or stainless steel for industrial panels; nylon multi-hole variants appear on lighter-duty and plastic enclosures.

Product example: XingWei nickel-plated brass multi-hole cable gland (XW-DK series), IP68.

When Multi-Hole Glands Make Sense

Multi-hole glands are a packaging choice, not a substitute for correct IP rating, thread match, or cable OD. Each hole still has a clamping range; cables outside that range will not seal.

When to Prefer Single Glands Instead

How to Size a Multi-Hole Gland

1. Count the cables that will share the entry now—and any spare holes you truly need. Empty holes must be closed with the manufacturer’s blank pins or plugs; an open hole in the insert voids the seal.

2. Measure every cable OD on the finished jacket. All cables must fall inside the published range for their holes. Do not force a cable that is too large; do not leave a hole “almost closed” on a cable that is too small.

3. Match hole pattern to the insert — same-diameter holes vs mixed-diameter inserts. Order the insert that matches your cable set; do not assume any multi-hole body accepts any OD mix.

4. Confirm thread and entry hole — Metric, NPT, PG, or other, same rules as single glands. Wrong thread still destroys the panel-side seal.

5. Check IP rating and material for the environment (indoor, outdoor, wash-down, coastal). Multi-hole does not automatically mean a higher or lower IP; performance depends on correct assembly and the datasheet rating.

Installation Notes

General waterproof install practice still applies: square body, entry washer where required, measured torque, seal on the outer sheath only. See How to Install a Waterproof Cable Gland.

Extra points for multi-hole:

If water appears after install, check OD match and blanking first, then torque and entry washer—see Cable Gland Leaking Water? and installation mistakes that cause IP68 ingress.

Common Specification Mistakes

Multi-Hole vs Multiple Single Glands

Multi-hole glandMultiple single glands
Panel cut-outsOneOne per cable
Best cable setSeveral similar ODsAny mix of ODs
Service one cableMay disturb othersIndependent
Armour / EMCUsually notAvailable per cable
Spare capacityBlank pins requiredBlanking plugs on spare holes

Choose multi-hole for space and cable similarity. Choose single glands for flexibility, armour, EMC, or frequent individual replacement.

Frequently Asked Questions

What is a multi-hole cable gland?

A multi-hole cable gland is a single entry fitting with a sealing insert that accepts two or more cables. One body mounts in one panel hole; each cable sits in its own hole in the elastomer and is sealed when the compression nut is tightened.

Can I leave some holes empty in a multi-hole gland?

Only if you close them with the blanking pins or plugs specified by the manufacturer. An open hole prevents the assembly from achieving its rated IP seal.

Can cables of different diameters share one multi-hole gland?

Only if the insert is designed with different hole sizes that match each cable OD. A single-size multi-hole insert requires all cables to fall within the same clamping range.

Are multi-hole glands IP68?

Many industrial multi-hole glands are rated IP68 when correctly assembled with the right cable ODs and blanked spare holes. The rating is not automatic—follow the datasheet ranges and install steps. For IP rating meaning, see IP68 Cable Gland Explained.


Multi-hole cable glands reduce cut-outs when several similar cables enter the same point. Size every hole to measured jacket OD, blank unused openings, and keep armour or EMC needs on dedicated single glands. Explore options such as the XingWei XW-DK multi-hole series in the cable gland category, or request a quote with cable count, each OD, thread, and IP target.