Specifying a normal industrial gland on SWA cable is a common procurement error. The outer seal may look closed, but the armour is free to pull out and the earth path through the armour is undefined. This guide explains when you need an armored (typically double-compression) gland, how it differs from single-compression types, and what to check on the datasheet before order.
For general cable gland basics, see What Is a Cable Gland?. For outdoor IP selection, see IP68 Cable Gland Explained.
What Is Cable Armour and Why the Gland Changes
SWA (steel-wire armour) is a layer of galvanised steel wires wound over an inner sheath. It is widely used on industrial power and distribution cables for mechanical protection and, in many designs, as a circuit protective conductor path when correctly terminated.
AWA (aluminium-wire armour) uses aluminium wires instead of steel—common where weight or non-magnetic behaviour matters. Termination practice is similar in principle: the armour must be clamped, not left floating inside a single outer seal.
On unarmoured cable, a single-compression gland is enough: one elastomer seal compresses onto the outer sheath for IP performance and strain relief. On armoured cable you usually need a second clamping stage that locks the armour wires (or tape) so pull-out force is taken by the gland body and, where specified, transferred to the enclosure earth.
Single Compression vs Double Compression
Single-compression glands
Single-compression glands have one seal zone on the outer sheath. They suit unarmoured control, instrument, and power cables in ordinary panels. They are the correct choice for most indoor automation and many outdoor unarmoured runs—see standard and waterproof ranges in the XingWei cable gland category.
They are not a substitute for armour termination. Putting SWA through a single-compression gland leaves the armour uncontrolled and often prevents a proper outer seal because the armour diameter and outer sheath diameter fall in different zones of the cable build-up.
Double-compression (armored) glands
Double-compression glands provide two distinct actions:
- Inner seal / armour clamp — after the outer sheath is cut back, the armour is spread or seated into a clamp ring (or equivalent). Tightening this stage grips the armour for mechanical retention and earth continuity to the metal gland body.
- Outer seal — a second elastomer compresses onto the outer sheath (or a dedicated outer jacket zone) to restore environmental sealing.
Some designs also seal on the inner sheath under the armour. Always follow the manufacturer’s strip lengths and assembly order; the sequence is part of achieving both pull-out strength and IP rating.
Explosion-proof armored entries add further rules (flamepath, certified arrangement, earth tag). For hazardous areas, use the dedicated guides: Explosion Proof Cable Glands in Hazardous Areas and How to Select an Explosion-Proof Cable Gland—and confirm the certificate covers the exact gland and cable type.
How an Armored Cable Gland Is Installed (Overview)
Exact strip dimensions and torque values come from the datasheet for the part number you hold. The usual logic is:
- Confirm cable type — SWA or AWA, inner sheath OD, armour OD, outer sheath OD. Select a gland whose published ranges cover each layer you will clamp or seal.
- Cut and strip to drawing — expose armour over the length the clamp requires; leave outer sheath under the outer seal; leave inner sheath intact where an inner seal is used.
- Fit armour clamp — seat wires evenly into the clamp ring; avoid crossed wires and missing strands that create a weak pull-out path.
- Tighten armour stage — to the specified torque so the armour cannot withdraw and the metal path to the body is sound.
- Make the outer (and inner) seals — compress elastomers onto the correct sheath layers only.
- Earth continuity — where the armour is used as a CPC or equipotential bond, verify continuity from armour to enclosure earth (earth tag or locknut arrangement as specified).
- Panel entry — thread, locknut, and entry washer must still match the enclosure, same as any other gland.
General waterproof install discipline (square body, no cross-threading, no over-crushing of rubber) still applies—see How to Install a Waterproof Cable Gland for the single-seal sequence and torque caution. Armored glands simply add the armour stage; they do not relax IP or thread rules.
Selection Checklist for Armored Glands
Use this list when writing the bill of materials:
- Cable construction — SWA, AWA, or tape armour; number of cores; voltage class if relevant to stripping practice.
- Layer diameters — inner sheath, over-armour, outer sheath. Match each to the gland’s published ranges.
- Environment — indoor, outdoor, coastal, wash-down. Choose brass, nickel-plated brass, or stainless accordingly.
- IP rating — as required for the enclosure location (IP66/67/68 as appropriate).
- Thread — Metric, NPT, PG, etc., matching the entry hole.
- Earth arrangement — whether armour must be bonded; need for earth tag or conductive path through the body.
- Hazardous area — if the location is classified, the gland must carry the correct protection concept and certificate scope—not only “armored” in the catalogue name.
Material comparison for non-armour duty is covered in Brass vs Nylon vs Stainless Steel. Nylon single-compression glands are rarely the right product for SWA power cables; metal double-compression bodies are the usual industrial choice.
Common Specification and Field Mistakes
Ordering a standard waterproof gland for SWA “because it is IP68.” IP rating does not equal armour clamp. Without an armour stage, pull-out and earthing remain unresolved.
Sizing only on outer sheath OD. The armour clamp range and inner seal range must fit as well. A gland that seals the outer jacket but cannot accept the armour diameter will not assemble correctly.
Leaving armour wires uneven or short. Partial engagement in the clamp reduces pull-out strength and can leave sharp ends that damage the outer seal.
Skipping earth verification. On circuits that rely on armour as a protective path, continuity from armour to the enclosure earth bar must be proven after install.
Using the wrong strip length. Too little armour in the clamp, or outer sheath ending inside the wrong chamber, is a frequent cause of both mechanical and IP failure.
Assuming “armored gland” means Ex certified. Armour capability and explosion-proof certification are separate. Hazardous locations need both the mechanical arrangement and the certificate that matches zone and gas/dust group.
When You Still Use Single-Compression on “Tough” Sites
Not every harsh environment needs a double-compression gland. Unarmoured cable in outdoor, wash-down, or coastal service needs the correct IP rating and material (often nickel-plated brass or stainless)—not an armour clamp. Conversely, indoor SWA still needs an armored gland for termination even if the IP requirement is modest. Match the gland to the cable construction first, then to the environment.
Frequently Asked Questions
What is the difference between a single and double compression cable gland?
A single-compression gland seals and grips the outer sheath only. A double-compression gland adds a second stage that clamps the metallic armour (and often seals the inner sheath), providing pull-out strength and earth continuity for SWA/AWA cable.
Can I use a normal cable gland on SWA cable?
No. A standard single-compression gland does not clamp the armour. The armour can pull out under load, and earth continuity through the armour is not properly established. Use a gland designed for armoured cable and install it to the manufacturer’s strip and torque instructions.
Does an armored cable gland provide earth continuity?
Metal armored glands are designed so that, when the armour is correctly clamped, a conductive path exists from the armour through the gland body to the earthed enclosure (often via locknut or earth tag). Always verify continuity after installation when the armour is part of the protective earthing arrangement.
Are armored cable glands the same as explosion-proof glands?
Not necessarily. “Armored” describes the mechanical clamp for SWA/AWA. “Explosion-proof” (Ex) describes a certified protection concept for hazardous areas. Some products are both; many are only one or the other. Read the certificate and the cable-type scope before specifying for Zone/Division locations.
Armored cable glands exist because SWA and AWA cables have a metallic layer that must be clamped and, where required, earthed—not only sealed. Choose double compression when armour is present; size every layer of the cable; follow strip lengths and torque; and keep hazardous-area certification as a separate, explicit check. Browse industrial and explosion-oriented options under the XingWei cable gland range (including double-compression and BDM-series entries where applicable), or request a quote with cable construction, layer ODs, thread, material, and IP or Ex requirements.